Warranty : Up to 5-year limited warranty
Max. Operating Pressure : Up to 300 psi (20,68 bar)
Process Temperature Range : Based on fill fluid: Maximum 401°F (205°C), Minimum -157°F (-105°C)
Communication Protocol : 4-20 MA HART®, WirelessHART®, FOUNDATION™ fieldbus, PROFIBUS® PA, 1-5 V Low Power HART®
Seal System Type : Direct Mount, Tuned-System
Transmitter Connection : Welded-Repairable
Process Connection : Flanged: ANSI/ASME, EN/DIN, JIS
Process Wetted Material : 316L SST, Alloy C-276, Tantalum
Diagnostics : Basic Diagnostics, Process Alerts, Loop Integrity Diagnostics, Plugged Impulse Line Diagnostics
Certifications/Approvals : SIL 2/3 certified to IEC 61508 by an independent 3rd party, NACE®, hazardous location, see full specs for complete list of certifications
Wireless Update Rate : 1 sec. to 60 min., user selectable
Power Module Life : Up to 10-year life, field replaceable (order separately)
Wireless Range : Internal antenna (225 m)